The provisions of Section 905 of IEBC are adopted by reference with the following modification:
1. Revise Section 905.2 to read:
"905.2 Means-of-egress lighting.
Means of egress from the highest work area story to the level of exit discharge shall be provided with artificial lighting within the exit enclosure in accordance with the requirements of the Chicago Building Code and Chicago Electrical Code."
2. Revise Section 905.3 by replacing "work area floor to the floor of exit discharge" with "work area story to the level of exit discharge."
(Amend Coun. J. 2-19-20, p. 14473, Art. IV, § 20)