The provisions of Section 1205 of IFC are adopted by reference with the following modifications:
1. Delete Section 1205.2.
2. Revise Section 1205.3, item 3, excluding its subitems, to read:
"3. Field-fabricated fuel cell power systems shall be accepted based on a review of a technical report. The report shall be prepared by and bear the stamp of a registered design professional and shall include:"
3. Revise Section 1205.5 to read:
"1205.5 Residential use.
Stationary fuel cell power systems shall not be installed in Group R-3, R-4 or R-5 buildings, or dwelling units associated with Group R-2 buildings unless they are specifically listed for residential use."
4. Revise Section 1205.13 by deleting "in approved locations."