14B-33-3302 Construction safeguards.
The provisions of Section 3302 of IBC are adopted by reference with the following modifications:
1.   Revise Section 3302.1, excluding the exceptions, to read:
"3302.1 Alterations, repairs and additions.
Required means of egress components, existing structural elements, fire protection devices and sanitary safeguards shall be maintained at all times during alterations, repairs or additions to any building or structure."
2.   Delete Section 3302.2.
3.   Delete Section 3302.3.
4.   Add a new Section 3302.4 to read:
"3302.4 Construction loads.
Provisions shall be made to ensure that stresses due to wind loads, dead loads and loads due to material storage and construction equipment imposed during the construction, alteration, repair, addition to or demolition of any structure shall not exceed the allowable stresses for materials as limited by the provisions of this code."
5.   Add a new Section 3302.5 to read:
"3302.5 Protection of openings.
All stairways, elevator shafts, flues, and other vertical openings in the floors and roof shall be covered or properly protected."