The provisions of Section 2610 of IBC are adopted by reference with the following modifications:
1. In provisions adopted by reference, reset the following terms in italic type: "approved"; "light-transmitting plastic roof panels"; "roof covering" and "unit skylight."
2. Revise exception 1 to Section 2610.2 to read:
"1. Curbs shall not be required for skylights used on roofs having a minimum slope of three units vertical in 12 units horizontal (25-percent slope) in occupancies in Group R-3 or R-5 and on buildings with a nonclassified roof covering."
3. Revise the exception to Section 2610.4 to read:
"Exception: The area limitation shall not apply where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1."
4. Revise the exception to Section 2610.5 to read:
"Exception: The aggregate area limitations of light-transmitting plastic skylights shall be increased 100 percent beyond the limitations set forth in this section where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1."
5. Revise exception 2 to Section 2610.6 to read:
"2. In Group R-3 or R-5, multiple skylights located above the same room or space with a combined area not exceeding the limits set forth in Section 2610.4."