14B-26-2608 Light-transmitting plastic glazing.
The provisions of Section 2608 of IBC are adopted by reference with the following modifications:
1.   Revise item 2 to section 2608.2, excluding its exception, to read:
"2.   Flame barriers extending 30 inches (762 mm) beyond the exterior wall in the plane of the floor, or vertical panels not less than 4 feet (1219 mm) in height, shall be installed between glazed units located in adjacent stories."
2.   Revise item 3 to section 2608.2, including its exception, to read:
"3.   Light-transmitting plastics shall not be installed more than 40 feet (12 190 mm) above grade plane."