The provisions of Section 1105 of IBC are adopted by reference with the following modifications:
1. Add a new exception 3 to Section 1105.1 to read:
"3. In multi-story housing, at least 50 percent of all public entrances shall be accessible."
2. Add a new Section 1105.2 to read:
"1105.2 Entrances to rooms or spaces.
Within a building or facility, all required doors, doorways and gates on an accessible route which serve accessible rooms or spaces shall be accessible."
3. Add a new Section 1105.3 to read:
"1105.3 Group I-2 and ambulatory care facilities.
In Group I-2 occupancies and Group B ambulatory care facilities at least one accessible entrance shall be protected from the weather by a canopy or roof overhang. Such entrance shall incorporate a passenger loading zone complying with Section 1106.7."
4. Add a new Section 1105.4 to read:
"1105.4 Power-operated doors.
At least one accessible entrance door to the following facilities, or each door where the entrance consists of doors in series, shall be a power-operated door complying with Section 1010.1.4.2:
1. Governmental facilities which contain or provide administrative services available to the general public.
2. Museums with a gross floor area of 5,000 square feet (465 m2) or more.
3. Passenger terminals.
4. High-rise buildings containing Accessible units or Type A units.
5. Group E-1 occupancies."