14B-10-1028 Exit discharge.
The provisions of Section 1028 of IBC are adopted by reference with the following modifications:
1.   Revise exception 1 to Section 1028.1 by replacing "through areas on the level of discharge" with "through a lobby or similar common area on the level of exit discharge."
1.1.   Revise exception 1.1 to Section 1028.1 by replacing "from the point of termination of the enclosure." with "within 25 feet (7620 mm) and no more than two turns, each not exceeding 90 degrees (1.57 rad), from the point of termination of the enclosure. There shall be no dead-end corridors or similar conditions exceeding 10 feet (3048 mm) in length adjacent to the point of termination of the enclosure."
1.2.   Revise exception 1.3 to Section 1028.1 by deleting "approved."
2.   Add a new exception 4 to Section 1028.1 to read:
"4.   Up to 100 percent of the number, minimum width, and required capacity of interior exit stairways and exterior exit ramps is permitted to egress through a lobby or similar common area on the level of exit discharge provided that all of the following conditions are met:
4.1.   Discharge of interior exit stairways and exterior exit ramps shall be provided with a free and unobstructed path of travel to at least two distinct exterior exit doors and each exterior exit door is readily visible and identifiable within 25 feet (7620 mm) and no more than two turns, each not exceeding 90 degrees (1.57 rad), from the point of termination of the enclosure. There shall be no dead-end corridors or similar conditions exceeding 10 feet (3048 mm) in length adjacent to the point of termination of the enclosure.
4.2.   The entire area of the level of exit discharge is separated from areas below by construction conforming to the fire-resistance rating for the enclosure.
4.3.   The building is protected throughout by an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
4.4.   Means of egress components are separated in accordance with Exception 1.4."
3.   Revise Section 1028.3 to read:
"1028.3 Exit discharge components.
Exterior exit discharge components shall be sufficiently open to the atmosphere so as to minimize the accumulation of smoke and toxic gases."
4.   Revise Section 1028.4.1 by replacing "Group R-3 and U occupancies" with "Group R-3, R-5 and U occupancies and Group R-2 occupancies in buildings with no more than 4 stories above grade plane."
5.   Revise exception 2 to Section 1028.4.2 by replacing "Group R-3" with "Group R-3 or R 5."
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 52; Amend Coun. J. 1-26-22, p. 43756, Art. II, § 11; Amend Coun. J. 12-14-22, p. 58278, Art. III, § 5)