The provisions of Section 1021 of IBC are adopted by reference with the following modification:
1. Revise Section 1021.4 to read:
"1021.4 Location.
Exterior egress balconies shall have a minimum fire separation distance of 10 feet (3048 mm) measured at right angles from the exterior edge of the egress balcony to:
1. The closest abutting property line.
2. The far side of a public way.
3. The exterior walls of other buildings on the same lot with openings that are not protected in accordance with Section 705 based on fire separation distance."