The provisions of Section 1020 of IBC are adopted by reference with the following modifications:
1. Delete exception 1 to Section 1020.1.
2. Replace Table 1020.1 as shown:
TABLE 1020.1
CORRIDOR FIRE-RESISTANCE RATING
CORRIDOR FIRE-RESISTANCE RATING
OCCUPANCY
|
OCCUPANT LOAD SERVED BY CORRIDOR
|
REQUIRED FIRE-RESISTANCE RATING (hours)
| |
Without sprinkler system | With sprinkler system
|
OCCUPANCY
|
OCCUPANT LOAD SERVED BY CORRIDOR
|
REQUIRED FIRE-RESISTANCE RATING (hours)
| |
Without sprinkler system | With sprinkler system
| ||
H-1, H-2, H-3 | All | Not Permitted | 1 |
H-4, H-5 | Greater than 30 | Not Permitted | 1 |
A, B, F, M, S, U | Greater than 30 | 1 | 0 e |
E | All | 1 | 1 |
R | Greater than 10 | 1 | 1 |
I-2 a | All | Not Permitted | 0 |
I-1, I-3 | All | Not Permitted | 1 b |
I-4 | All | 1 | 0 |
a. For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3.
b. For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8.
c. [Reserved.]
d. [Reserved.]
e. In Groups A-1, A-2, A-3, and A-4 occupancies, corridors serving and visually separated from a room or suite of rooms with an occupant load of 300 or more shall have a fire-resistance rating of not less than 1 hour.
2.1. Revise Section 1020.1.1 by replacing "Section 3006.2.1" with "Section 3002.1.1."
3. Replace Table 1020.2 as shown:
TABLE 1020.2
MINIMUM CORRIDOR WIDTH
MINIMUM CORRIDOR WIDTH
OCCUPANCY
| MINIMUM WIDTH (inches) |
OCCUPANCY
| MINIMUM WIDTH (inches) |
Any facility not listed in this table | 44 |
Access to and utilization of mechanical, plumbing or electrical systems or equipment | 24 |
With an occupant load of less than 50 | 36 |
Within or serving a single dwelling unit | 36 |
In Group E-1 corridors serving classrooms, study rooms or assembly rooms | 60 a |
In corridors and areas serving stretcher traffic in ambulatory care facilities | 72 |
Group I-2 in areas where required for bed movement | 96 |
For SI: 1 inch = 25.4 mm.
a. When lockers are installed in corridors, the full required clear width of the corridor shall be provided between locker doors when open.
4. Revise exception 2 to Section 1020.4 to read:
"2. In occupancies in Groups B, E-2, F, I-1, M, R, S and U, where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the length of the dead-end corridors shall not exceed 50 feet (15 240 mm)."
5. Revise exception 1 to Section 1020.5 by deleting "smoking lounges."
6. Add new exception 5 to Section 1020.5 to read:
"5. Use of a corridor as a source of makeup air for exhaust systems in Group R-2 dwelling units and sleeping units that open directly onto such corridors shall be permitted, provided that each such corridor is directly supplied with outdoor air at a rate greater than the rate of makeup air taken from the corridor and the dwelling units and sleeping units are provided with an independent source of air for ventilation."
7. Delete item 5 in Section 1020.5.1.
8. Add a new Section 1020.7 to read:
"1020.7 Toilet rooms.
Separation shall not be required between a toilet room and a fire-resistance-rated corridor where the toilet room meets the following criteria:
1. The toilet room shall be separated from the remainder of the building by fire-resistance-rated construction meeting the requirements of Section 1020.1.
2. The toilet room shall not directly connect to any habitable space.
3. The toilet room shall not contain any fuel-fired equipment or appliances."