The provisions of Section 718 of IBC are adopted by reference with the following modifications:
1. Delete item 8 in Section 718.2.1.
2. Revise Section 718.2.1.3 to read:
"718.2.1.3 Loose-fill insulation material.
Loose-fill insulation material, insulating foam sealants and caulk materials shall not be used as a fireblock."
3. Revise Section 718.2.6 by replacing "approved wood of natural decay resistance" with "naturally durable wood."
4. Revise Section 718.2.7 by replacing "an approved material" with "a noncombustible material."
5. Delete the exception to Section 718.4.