14B-7-717 Ducts and air transfer openings.
The provisions of Section 717 of IBC are adopted by reference with the following modifications:
1.   Revise the title of Section 717.1.1 to "Transfer ducts."
2.   Delete Section 717.2.1.
3.   Revise the first sentence of Section 717.4 to read:
"Fire and smoke dampers shall be provided with a means of access that is large enough to allow inspection and maintenance of the damper and its operating parts."
4.   Revise Section 717.5.1 to read:
"717.5.1 Fire walls.
Ducts and air transfer openings permitted in fire walls in accordance with Section 706.11 shall be protected with listed 3-hour-rated fire dampers installed on both sides of the fire wall in accordance with their listing."
5.   Revise exception 2 to Section 717.5.2 by replacing "an approved" with "a."
6.   Revise Section 717.5.3 by replacing "fire and smoke dampers" with "fire dampers."
7.   Delete exceptions 2, 3 and 4 to Section 717.5.2.
8.   Revise exception 5 to Section 717.5.2 to read:
"5.   Fire dampers are not required in kitchen and clothes dryer exhaust systems."
9.   Revise Section 717.5.4 by replacing "Ducts and air transfer openings" with "Air transfer openings."
10.   Delete the exceptions to Section 717.5.4.
11.   Delete Section 717.5.4.1.
12.   Revise Section 717.5.5 by replacing "at each point" with "adjacent to each point."
13.   Add a new exception to Section 717.5.6 to read:
"Exception: Fire dampers are not required in residential kitchen and clothes dryer exhaust systems."
14.   Delete Section 717.5.7.
15.   Revise Section 717.6.1 by deleting "approved."
16.   Revise the exception to Section 717.6.1 by replacing "three floors" with "four floors."
17.   Revise Section 717.6.2 by deleting "approved."
18.   Revise Section 717.6.3 to read:
"717.6.3 Nonfire-resistance-rated floor assemblies.
Duct systems constructed of materials in accordance with the Chicago Mechanical Code that penetrate nonfire- resistance-rated floor assemblies shall be protected by any of the following methods:
1.   A shaft enclosure in accordance with Section 713.
2.   The annular space around the penetrating duct is protected with a noncombustible material that resists the free passage of flame and the products of combustion.
Exception: Fire dampers are not required in ducts within individual residential dwelling units."
19.   Add a new exception to Section 717.7.
"Exception: Within individual Group R dwelling units or sleeping units."