14B-7-703 Fire-resistance ratings and fire tests.
The provisions of Section 703 of IBC are adopted by reference with the following modifications:
1.   Delete Section 703.2.5.
2.   Revise the numbered portion of Section 703.3 to read:
"1.   Fire-resistance designs documented in a test report prepared by an approved agency or test results compiled in the UL Online Certifications Directory, Intertek Directory of Building Products, GA 600 or another approved source.
2.   Prescriptive designs of fire-resistance-rated building elements, components or assemblies as prescribed in Section 721.
3.   Approved calculations in accordance with Section 722.
4.   Approved engineering analysis based on a comparison of building element, component or assembly designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E119 or UL 263."
3.   Delete the last sentence of Section 703.4.
4.   Revise the first sentence of Section 703.7 to read:
"Where there is an accessible concealed floor, floor-ceiling or attic space and within mechanical and electrical rooms, fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other wall required to have protected openings or penetrations shall be effectively and permanently identified with signs or stenciling in the concealed space or mechanical or electrical room."