18-29-916.5.1  Sewage pumps and sewage ejectors other than pneumatic.
   Drainage piping below sewer level shall be vented in a similar manner to that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 18-29-916.5.1.
Table 18-29-916.5.1
Size and Length of Sump Vents
Discharge Capacity of Pump (gpm)
Maximum Developed Length of Vent (feet) a
Diameter of vent (inches)
1 1/4
1 1/2
2
2 1/2
3
4
Discharge Capacity of Pump (gpm)
Maximum Developed Length of Vent (feet) a
Diameter of vent (inches)
1 1/4
1 1/2
2
2 1/2
3
4
10
No limit b
No limit
No limit
No limit
No limit
No limit
20
270
No limit
No limit
No limit
No limit
No limit
40
72
160
No limit
No limit
No limit
No limit
60
31
75
270
No limit
No limit
No limit
80
16
41
150
380
No limit
No limit
100
10 c
25
97
250
No limit
No limit
150
N.P.
10 c
44
110
370
No limit
200
N.P.
N.P.
20
60
210
No limit
250
N.P.
N.P.
10
36
132
No limit
300
N.P.
N.P.
10 c
22
88
380
400
N.P.
N.P.
N.P.
10 c
44
210
500
N.P.
N.P.
N.P.
N.P.
24
130
 
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m.
a Developed length plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Suggested allowances shall be obtained from NBS Monograph 31 or other approved sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not available.
b Actual values greater than 500 feet.
c Less than 10 feet.