Drainage piping below sewer level shall be vented in a similar manner to that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 18-29-916.5.1.
Discharge Capacity of Pump (gpm) | Maximum Developed Length of Vent (feet) a | |||||
Diameter of vent (inches) | ||||||
1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 4 |
Discharge Capacity of Pump (gpm) | Maximum Developed Length of Vent (feet) a | |||||
Diameter of vent (inches) | ||||||
1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 4 | |
10 | No limit b | No limit | No limit | No limit | No limit | No limit |
20 | 270 | No limit | No limit | No limit | No limit | No limit |
40 | 72 | 160 | No limit | No limit | No limit | No limit |
60 | 31 | 75 | 270 | No limit | No limit | No limit |
80 | 16 | 41 | 150 | 380 | No limit | No limit |
100 | 10 c | 25 | 97 | 250 | No limit | No limit |
150 | N.P. | 10 c | 44 | 110 | 370 | No limit |
200 | N.P. | N.P. | 20 | 60 | 210 | No limit |
250 | N.P. | N.P. | 10 | 36 | 132 | No limit |
300 | N.P. | N.P. | 10 c | 22 | 88 | 380 |
400 | N.P. | N.P. | N.P. | 10 c | 44 | 210 |
500 | N.P. | N.P. | N.P. | N.P. | 24 | 130 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m.
a Developed length plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Suggested allowances shall be obtained from NBS Monograph 31 or other approved sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not available.
b Actual values greater than 500 feet.
c Less than 10 feet.