18-29-608.1  General.
   A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from nonpotable liquids, solids or gases being introduced into the potable water supply through cross-connections or any other piping connections to the system. Backflow preventer applications shall conform to Table 18-29-608.1.
Table 18-29-608.1
Application for Backflow Preventers
For a printer-friendly PDF version of Table 18-29-608.1, please click here.
Device
Degree of Hazard a
Application b
Applicable Standards
Device
Degree of Hazard a
Application b
Applicable Standards
Air gap c
High or low hazard
Backsiphonage or backpressure
ASME A112.1.2
Antisiphon-type Water Closet Flush Tank Ball Cock
Low Hazard
Backsiphonage only
ASSE 1002
CSA CAN/CSA-B125
Reduced Pressure Principle Backflow Preventer
High or low hazard
Backpressure or backsiphonage
Sizes 1/4" to 10"
ASSE 1013
AWWA C511
CSA CAN/CSA B64.4
Reduced Pressure Detector Assembly Backflow Preventer
High or low hazard
Backsiphonage or backpressure
ASSE 1047
Double Check Backflow Prevention Assembly
Low hazard
Backpressure or backsiphonage
Sizes 3/8" to 16"
ASSE 1015
AWWA C510
Double Check Detector Backflow Preventer Assembly
Low hazard
Backpressure or backsiphonage (Fire sprinkler systems)
Sizes 1 1/2" - 16"
ASSE 1048
Dual Check Valve-Type Backflow Preventer
Low hazard
Backpressure or backsiphonage
Sizes 1/4" - 1"
ASSE 1024
Backflow Preventer with Intermediate Atmospheric Vents
Low hazard
Backpressure or backsiphonage
Sizes 1/4" - 3/4"
ASSE 1012
CSA CAN/CSA-B64.3
Dual Check Valve-Type Backflow Preventer for Carbonated Beverage Dispensers/Post Mix Type
Low hazard
Backpressure or backsiphonage
Sizes 1/4" - 3/8"
ASSE 1032
Pipe-Applied Atmospheric-Type Vacuum Breaker
High or low hazard
Backsiphonage only
Sizes 1/4" - 4"
ASSE 1001
CSA CAN/CSA-B64.1.1
Pressure Vacuum Breaker Assembly
High or low hazard
Backsiphonage only
Sizes 1/2" - 2"
ASSE 1020
Hose-connection Vacuum Breaker
High or low hazard
Backsiphonage
Sizes 1/2", 3/4", 1"
ASSE 1011
CSA CAN/CSA-B64.2
Vacuum Breaker Wall Hydrants, Frost-Resistant, Automatic Draining Type
High or low hazard
Backsiphonage
Sizes 3/4", 1"
ASSE 1019
CSA CAN/CSA-B64.2.2
Laboratory Faucet Backflow Preventer
(Non-testable)
Low hazard
Backsiphonage
ASSE 1035
CSA B64.7
Hose Connection Backflow Preventer
(Non-testable)
Low hazard
Low head backpressure, rated working pressure
backpressure or backsiphonage
Sizes 1/2" - 1"
ASSE 1052
Spill-proof vacuum breaker
High or low hazard
Backsiphonage only
Sizes 1/4" - 2"
ASSE 1056
 
For SI: 1 inch = 25.4 mm
a   Low Hazard - See Pollution (Section 202) and Department of Water Management requirements
     High Hazard - See Contamination (Section 202) and Department of Water Management requirements
b   See Backpressure (Section 202)
     See Backpressure, Low Head (Section 202)
     See Backsiphonage (Section 202)
c   Break tank
d   For systems using non-food grade chemical additives
(Amend Coun. J. 11-8-12, p. 38872, § 353)