You are viewing an archived code
Water distribution pipe shall conform to NSF 61 and shall conform to one of the standards listed in Table 18-29-605.5. All hot water distribution pipe and tubing shall have a minimum pressure rating of 100 psi (690 kPa) at 1805°F (825°C).
Material | Standard |
Material | Standard |
Brass pipe | ASTM B 43 |
Chlorinated Polyvinyl Chloride (CPVC) plastic pipe and tubing
a
| ASTM D 2846; ASTM F 441; ASTM F 442; CSA B 137.6 |
Polypropylene (PP) plastic pipe and tubing a | ASTM F 1412 |
PVDF plastic pipe and tubing a | ASTM F 1412 |
Copper or copper-alloy pipe | ASTM B 42; ASTM B 302 |
Copper or copper-alloy tubing (Type K, L, or M) | ASTM B 74; ASTM B 88; ASTM B 251; ASTM B 447 |
Galvanized steel pipe | ASTM A 53 |
a For secondary water used in process applications only.