18-29-308.5  Interval of support.
   Pipe shall be supported in accordance with Table 18-29-308.5.
Table 18-29-308.5
Hanger Spacing
 
Piping Material
Maximum Horizontal Spacing (feet)
Maximum Vertical Spacing (feet)
Brass pipe
10
15
Cast-iron pipe a
5
15
Copper or copper-alloy pipe
12
10
Copper or copper-alloy tubing, 1 1/4-inch diameter and smaller
6
10
Copper or copper-alloy tubing, 1 1/2-inch diameter and larger
10
10
PVC pipe
4
4
 
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm
a The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed.
(Amend Coun. J. 3-27-02, p. 82090, § 3)