Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
CHAPTER 18-28 MECHANICAL SYSTEMS*
Article I. Administration (18-28-101 et seq.)
Article II. Definitions (18-28-201 et seq.)
Article III. General Regulations (18-28-301 et seq.)
Article IV. Ventilation (18-28-401 et seq.)
Article V. Exhaust Systems (18-28-501 et seq.)
Article VI. Duct Systems (18-28-601 et seq.)
Article VII. Combustion Air (18-28-701 et seq.)
Article VIII. Chimneys and Vents (18-28-801 et seq.)
Article IX. Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment (18-28-901 et seq.)
Article X. Boilers, Water Heaters and Pressure Vessels (18-28-1001 et seq.)
Article XI. Refrigeration (18-28-1101 et seq.)
Article XII. Hydronic Piping (18-28-1200 et seq.)
Article XIII. Fuel Oil Piping and Storage (18-28-1301 et seq.)
Article XIV. Fuel-Gas Piping (18-28-1401 et seq.)
Article XV. Solar Systems (18-28-1501 et seq.)
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
18-28-703.3  Outdoor air.
   All air from outdoors. The confined space shall communicate with the outdoors in accordance with methods 1 or 2, which follow. The minimum dimension of air openings shall be not less than 3 in. (80 mm). If ducts are used, the ducts shall be of the same cross- sectional area as the free area of the openings to which they connect.
   1.   Two permanent openings, one commencing within 12 in. (300 mm) of the top of the enclosure and one commencing within 12 in. (300 mm) of the bottom of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or with attic spaces that freely communicate with the outdoors.
      (a)   If directly communicating with the outdoors or if communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in.2 per 4000 Btu/hr (550 mm 2/kW) of the total input rating of all equipment in the enclosure.
      (b)   If communicating with the outdoors through horizontal ducts, such opening shall have a minimum free area of not less than 1 in.2 per 2000 Btu/hr (1100 mm 2 /kW) of the total input rating of all equipment in the enclosure.
   2.   One permanent opening commencing within 12 in. (300 mm) of the top of the enclosure, shall be permitted if the equipment has clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (160 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate with the outdoors through a vertical or horizontal duct or space that freely communicate with the outdoors. The opening shall have a minimum free area as follows:
      (a)   1 in.2/3000 Btu/hr (700 mm 2 per kW) of the total input rating of all equipment located in the enclosure, and
      (b)   Not less than the sum of the areas of all vent connectors in the confined spaces.
18-28-704  Deliberately Omitted.
18-28-705  Engineered Installations.
18-28-705.1
   Engineered combustion air installations shall provide an adequate supply of combustion and dilution air and shall be approved by the authority having jurisdiction.
18-28-706  Forced Combustion Air Supply.
18-28-706.1  Mechanical combustion air supply for oil-fired appliances.
   Where all combustion air and dilution air is provided by a mechanical forced-air system, the combustion air and dilution air shall be supplied at the minimum rate of 1 cfm per 2,400 Btu/h [0.00067 m 3 /(s x kW)] of combined input rating of all the fuel-burning appliances served. Each of the appliances served shall be electrically interlocked to the mechanical forced-air system so as to prevent operation of the appliances when the mechanical system is not in operation. Where combustion air and dilution air is provided by the building's mechanical ventilation system, the system shall provide the specified combustion/dilution air rate in addition to the required ventilation air.
18-28-706.2  Mechanical combustion air supply for gas-fired appliances.
   Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from outdoors at the minimum rate of 0.35 ft 3 /min per 1,000 Btu/hr (0.034 3/mm per kW) for all appliances located within the space.
Loading...