Piping shall be either supported at distances not exceeding the spacing specified in Table 18-28-305.4, Piping Support Spacing.
Piping Material | Max. Horiz. Spacing (feet) | Max. Verti. Spacing (feet) |
Piping Material | Max. Horiz. Spacing (feet) | Max. Verti. Spacing (feet) |
ABS pipe | 4 | 10 c |
Aluminum pipe and tubing | 10 | 15 |
Brass pipe | 10 | 10 |
Brass tubing, 1 1/4-inch diameter and smaller | 6 | 10 |
Brass Tubing, 1 1/2-inch diameter and larger | 10 | 10 |
Cast-iron pipe b | 5 | 15 |
Copper or copper-alloy pipe | 12 | 10 |
Copper or copper-alloy tubing, 1 1/4-inch diameter and smaller | 6 | 10 |
Copper or copper-alloy tubing, 1 1/2-inch diameter and larger | 10 | 10 |
CPVC pipe or tubing, 1 inch and smaller | 3 | 10 c |
CPVC pipe or tubing, 1 1/4-inch and larger | 4 | 10 c |
Steel Pipe | 12 | 15 |
Steel Tubing | 8 | 10 |
Lead pipe | Continuous | 4 |
PB pipe or tubing | 2 2/3 (32 in.) | 4 |
PEX Tubing | 2 2/3 (32 in.) | 10 c |
PVC pipe | 4 | 10 c |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a See Section 18-28-301.14.
b The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed.
c Mid-story guide.