BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

CHAPTER 14E-8
COMMUNICATIONS SYSTEMS
14E-8-800   Communications circuits.
14E-8-810   Radio and television equipment.
14E-8-820   Community antenna television and radio distribution systems.
14E-8-830   Network-powered broadband communications systems.
14E-8-840   Premises-powered broadband communications systems.
14E-8-800  Communications circuits.
   The provisions of Article 800 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise subsection 800.110(A)(2) to read:
   “Communications Raceways. Communications wires and cables shall be permitted to be installed in plenum communications raceways, riser communications raceways, and general-purpose communications raceways selected in accordance with Table 800.154(b), listed in accordance with 800.182, and installed in accordance with 800.113.”
2.   Revise subsections 800.113(B) through (L) to read:
   “(B)   Ducts Specifically Fabricated for Environmental Air. Wires and cables installed in ducts specifically fabricated for environmental air shall be installed in accordance with 300.22(B).
   (C)   Other Spaces Used for Environmental Air (Plenums). Wires and cables installed in other spaces used for environmental air (plenums) shall be installed in accordance with 300.22(C).
   (D)   Risers – Cables, Raceways, and Cable Routing Assemblies in Vertical Runs. The following cables, raceways, and cable routing assemblies shall be permitted in vertical runs penetrating one or more floors and in vertical runs in a shaft:
      (1)   Types CMP and CMR cables
      (2)   Plenum and riser communications raceways
      (3)   Riser cable routing assemblies
      (4)   Types CMP and CMR cables installed in:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
      Informational Note: See 800.26 for firestop requirements for floor penetrations.
   (E)   Risers – Cables and Innerducts in Metal Raceways. The following cables and innerducts shall be permitted in metal raceways in a riser having firestops at each floor:
      (1)   Types CMP, CMR, CMG, CM, and CMX cables
      (2)   Plenum, riser, and general-purpose communications raceways
      (3)   Types CMP, CMR, CMG, CM, and CMX cables installed in:
         a.   Plenum communications raceways (innerduct)
         b.   Riser communications raceways (innerduct)
         c.   General-purpose communications raceways (innerduct)
      Informational Note: See 800.26 for firestop requirements for floor penetrations.
   (F)   Risers – Cables, Raceways, and Cable Routing Assemblies in Fireproof Shafts. The following cables, raceways, and cable routing assemblies shall be permitted to be installed in fire-proof riser shafts having firestops at each floor:
      (1)   Types CMP, CMR, CMG, CM, and CMX cables
      (2)   Plenum, riser, and general-purpose communications raceways
      (3)   Riser, and general-purpose cable routing assemblies
      (4)   Types CMP, CMR, CMG, and CM cables installed in:
         a.   Plenum, riser, and general-purpose communications raceways
         b.   Riser, and general-purpose cable routing assemblies
      Informational Note: See 800.26 for firestop requirements for floor penetrations.
   (G)   Risers – One- and Two-Family Dwellings. The following cables, raceways, and cable routing assemblies shall be permitted in one- and two-family dwellings:
      (1)   Types CMP, CMR, CMG, and CM cables
      (2)   Type CMX cables less than 0.25 in. in diameter
      (3)   Plenum, riser, and general-purpose communications raceways
      (4)   Riser, and general-purpose cable routing assemblies
      (5)   Types CMP, CMR, CMG, and CM cables installed in:
         a.   Plenum, riser, and general-purpose communications raceways
         b.   Riser, and general-purpose cable routing assemblies
   (H)   Cable Trays. The following wires, cables, and raceways shall be permitted to be supported by cable trays:
      (1)   Types CMP, CMR, CMG, and CM cables
      (2)   Plenum, riser, and general-purpose communications raceways
      (3)   Communications wires and Types CMP, CR, CMG, and CM cables installed in:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   General-purpose communications raceways
   (I)   Distributing Frames and Cross-Connect Arrays. The following wires, cables, raceways, and cable routing assemblies shall be permitted to be installed in distributing frames and cross-connect arrays:
      (1)   Types CMP, CMR, CMG, and CM cables and communications wires
      (2)   Plenum, riser, and general-purpose communications raceways
      (3)   Riser, and general-purpose cable routing assemblies
      (4)   Communications wires and Types CMP, CMR, CMG, and CM cables installed in:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   General-purpose communications raceways
         d.   Riser cable routing assemblies
         e.   General-purpose cable routing assemblies
   (J)   Other Building Locations. The following wires, cables, raceways, and cable routing assemblies shall be permitted to be installed in building locations other than the locations covered in 800.113(B) through (I):
      (1)   Types CMP, CMR, CMG, and CM cables
      (2)   A maximum of 3 m (10 ft) of exposed Type CMX in non-concealed spaces
      (3)   Plenum, riser, and general-purpose communications raceways
      (4)   Riser, and general-purpose cable routing assemblies
      (5)   Communications wires and Types CMP, CMR, CMG, and CM cables installed in:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   General-purpose communications raceways
      (6)   Types CMP, CMR, CMG, and CM cables installed in:
         a.   Riser cable routing assemblies
         b.   General-purpose cable routing assemblies
      (7)   Communications wires and Types CMP, CMR, CMG, CM, and CMX cables installed in raceways recognized in Chapter 3
      (8)   Type CMUC under-carpet communications wires and cables installed under carpet, modular tiles, and planks
   (K)   Multifamily Dwellings. The following cables, raceways, and cable routing assemblies shall be permitted to be installed in multifamily dwellings in locations other than the locations covered in 800.113(B) through (G):
      (1)   Types CMP, CMR, CMG, and CM cables
      (2)   Type CMX cables less than 0.25 in. in diameter in nonconcealed spaces
      (3)   Plenum, riser, and general-purpose communications raceways
      (4)   Riser, and general-purpose cable routing assemblies
      (5)   Communications wires and Types CMP, CMR, CMG, and CM cables installed in:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   General-purpose communications raceways
      (6)   Types CMP, CMR, CMG, and CM cables installed in:
         a.   Riser cable routing assemblies
         b.   General-purpose cable routing assemblies
      (7)   Communications wires and Types CMP, CMR, CMG, CM, and CMX cables installed in raceways recognized in Chapter 3
      (8)   Type CMUC under-carpet communications wires and cables installed under carpet, modular tiles, and planks
   (L)   One- and Two-Family Dwellings. The following cables, raceways, and cable routing assemblies shall be permitted to be installed in one- and two-family dwellings in locations other than the locations covered in 800.113(B) through 800.113(F):
      (1)   Types CMP, CMR, CMG, and CM cables
      (2)   Type CMX cables less than 6 mm (0.25 in.) in diameter
      (3)   Plenum, riser, and general-purpose communications raceways
      (4)   Riser, and general-purpose cable routing assemblies
      (5)   Communications wires and Types CMP, CMR, CMG, and CM cables installed in:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   General-purpose communications raceways
      (6)   Types CMP, CMR, CMG, and CM cables installed in:
         a.   Riser cable routing assemblies
         b.   General-purpose cable routing assemblies
      (7)   Communications wires and Types CMP, CMR, CMG, CM, and CMX cables installed in raceways recognized in Chapter 3
      (8)   Type CMUC under-carpet communications wires and cables installed under carpet, modular tiles, and planks
      (9)   Hybrid power and communications cable listed in accordance with 800.179(I)”
3.   Revise Table 800.154(a) to read:
Applications of Listed Communications Wires and Cables in Buildings
Applications
Wire and Cable Type
CMP
CMR
CMG
CM
CMX
CMUC
Hybrid power & Communication Cables
Communications Wires
Applications
Wire and Cable Type
CMP
CMR
CMG
CM
CMX
CMUC
Hybrid power & Communication Cables
Communications Wires
In ducts specifically fabricated for environmental air as described in 300.22(B)
In fabricated ducts
N
N
N
N
N
N
N
In metal raceway that complies with 300.22(B)
Y*
Y*
Y*
Y
N
N
N
In other spaces used for environmental air as described in 300.22(C)
In other spaces used for environmental air as described in 300.22(C)
N
N
N
N
N
N
N
In metal raceway that complies with 300.22(C)
Y*
Y*
Y*
Y*
N
N
Y*
In risers
In vertical runs
Y*
Y*
N
N
N
N
N
In metal raceways
Y*
Y*
Y*
Y
N
N
N
In fireproof shafts
Y*
Y*
Y*
Y
N
N
N
In plenum communications raceways
Y*
Y*
N
N
N
N
N
In riser communications raceways
Y*
Y*
N
N
N
N
N
In riser cable routing assemblies
Y*
Y*
N
N
N
N
N
In one- and two-family dwellings
Y*
Y*
Y*
Y
N
Y*
N
Within buildings in other than air-handling spaces and risers
General
Y*
Y*
Y*
Y
N
N
N
In one- and two-family dwellings
Y*
Y*
Y*
Y
Y
Y
Y
In multifamily dwellings
Y*
Y*
Y*
Y
Y
N
N
In nonconcealed spaces
Y*
Y*
Y*
Y
Y
N
N
Supported by cable trays
Y*
Y*
Y*
N
N
N
N
Under carpet or under floor covering, modular tiles & planks
N
N
N
N
Y*
N
N
In distributing frames and cross-connect arrays
Y*
Y*
Y*
N
N
N
Y
In any raceway recognized in Chapter 3
Y*
Y*
Y*
Y
N
N
Y
In plenum communications raceways
Y*
Y*
Y*
Y
N
N
Y
In riser communications raceways
Y*
Y*
Y*
Y
N
N
Y
In riser cable routing assemblies
Y*
Y*
Y*
Y
N
N
Y
In general-purpose communications raceways
Y*
Y*
Y*
Y
N
N
Y
In general-purpose cable routing assemblies
Y*
Y*
Y*
Y
N
N
Y
 
Note: An “N” indicates that the cable type is not permitted to be installed in the application. A “Y*” indicates that the cable type is permitted to be installed in the application subject to the limitations described in 800.113.
Informational Note No. 1: Part V of Article 800 covers installation methods within buildings. This table covers the applications of listed communications wires, cables, and raceways in buildings.
Informational Note No. 2: For information on the restrictions to the installation of communications cables in fabricated ducts, see 800.113(B).
4.   Revise Table 800.154(b) to read:
Applications of Listed Communications Raceways in Buildings
Applications
Listed Communications Raceway Type
Plenum
Riser
General- Purpose
Applications
Listed Communications Raceway Type
Plenum
Riser
General- Purpose
In ducts specifically fabricated for environmental air as described in 300.22(B)
In fabricated ducts
N
N
N
In metal raceway that complies with 300.22(B)
N
N
N
In other spaces used for environmental air (plenums) as described in 300.22(C)
In other spaces used for environmental air as described in 300.22(C)
N
N
N
In metal raceway that complies with 300.22(C)
Y*
Y*
Y*
In risers
In vertical runs
Y*
Y*
Y*
In metal raceways
Y*
Y*
Y*
In fireproof shafts
Y*
Y*
Y*
In riser cable routing assemblies
N
N
N
In one- and two-family dwellings
Y*
Y*
Y*
Within buildings in other than air-handling spaces and risers
General
Y*
Y*
Y*
In one- and two-family dwellings
Y*
Y*
Y*
In multifamily dwellings
Y*
Y*
Y*
In nonconcealed spaces
Y*
Y*
Y*
Supported by cable trays
Y*
Y*
Y*
Under carpet or under floor covering, modular tiles & planks
N
N
N
In distributing frames and cross-connect arrays
Y*
Y*
Y*
In any raceway recognized in Chapter 3
Y*
Y*
Y*
In riser cable routing assemblies
N
N
N
In general-purpose cable routing assemblies
N
N
N
 
Note: An “N” indicates that the communications raceway type shall not be permitted to be installed in the application. A “Y*” indicates that the communications raceway type shall be permitted to be installed in the application, subject to the limitations described in 800.110 and 800.113”
5.   Revise Table 800.154(c) to read:
Applications of Listed Cable Routing Assemblies in Buildings
Applications
Listed Communications Raceway Type
Riser
General- Purpose
Applications
Listed Communications Raceway Type
Riser
General- Purpose
In ducts specifically fabricated for environmental air as described in 300.22(B)
In fabricated ducts
N
N
In metal raceway that complies with 300.22(B)
N
N
In other spaces used for environmental air as described in 300.22(C)
In other spaces used for environmental air as described in 300.22(C)
N
N
In metal raceway that complies with 300.22(C)
Y*
Y*
In risers
In vertical runs
Y*
Y*
In metal raceways
Y*
Y*
In fireproof shafts
Y*
Y*
In riser cable routing assemblies
N
N
In one- and two-family dwellings
Y*
Y*
Within buildings in other than air-handling spaces and risers
General
Y*
Y*
In one- and two-family dwellings
Y*
Y*
In multifamily dwellings
Y*
Y*
In nonconcealed spaces
Y*
Y*
Supported by cable trays
Y*
Y*
Under carpet or under floor covering, modular tiles & planks
N
N
In distributing frames and cross-connect arrays
Y*
Y*
In any raceway recognized in Chapter 3
Y*
Y*
In riser cable routing assemblies
N
N
In general-purpose cable routing assemblies
N
N
 
Note: An “N” indicates that the cable routing assembly type shall not be permitted to be installed in the application. A “Y*” indicates that the cable routing assembly type shall be permitted to be installed in the application, subject to the limitations described in 800.110 and 800.113”
6.   Revise the first paragraph of Section 800.179 to read:
   “Communications wires and cables shall be listed in accordance with 800.179(A) through (H) and marked in accordance with Table 800.179. Conductors in communications cables, other than in a coaxial cable, shall be copper.”
7.   Delete subsection 800.179(I) and the subsequent informational note.
8.   Revise subsection 800.182(A) to read:
   “Plenum Communications Raceways. Plenum communications raceways shall be listed as having adequate fire-resistant and low-smoke-producing characteristics.”
9.   Revise Table 800.182(A) to read:
Cable Routing Assembly Markings
 
Type
Marking
Riser Cable Routing Assembly
Riser Cable Routing Assembly
General-Purpose Cable Routing Assembly
General-Purpose Routing Assembly
 
10.   Delete Informational Note No. 3 in subsection 800.182(A).
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-8-810  Radio and television equipment.
   The provisions of Article 810 of NFPA 70 are adopted by reference without modification.
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-8-820  Community antenna television and radio distribution systems.
   The provisions of Article 820 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise the first paragraph of section 820.24 to read:
   “Community television and radio distribution systems shall be installed in a neat and workmanlike manner. Coaxial cables installed exposed on the surface of ceiling and sidewalls shall be supported by the building structure in such a manner that the cables will not be damaged by normal building use. Such cables shall be secured by hardware including straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform to 300.4 and 300.11.”
2.   Delete Informational Note No. 2 under section 820.24, thereby renumbering Informational Note No. 3 as the new Informational Note No. 2.
3.   Revise subsection 820.110(A)(2) to read:
   “Communications Raceways. Coaxial cables shall be permitted to be installed in plenum communications raceways, riser communications raceways, and general- purpose communications raceways, selected in accordance with Table 800.154(b), listed in accordance with 800.182, and installed in accordance with 800.113.”
4.   Revise subsection 820.110(C) to read:
   “Cable Routing Assemblies. Coaxial cables shall be permitted to be installed in riser cable routing assemblies, and general-purpose cable routing assemblies selected in accordance with Table 800.154(c), listed in accordance with 800.182, and installed in accordance with 800.110(C) and 800.113.”
5.   Revise section 820.113 to read:
   “Installation of Coaxial Cables. Installation of coaxial cables shall comply with 820.113(A) through (K). Installation of raceways and cable routing assemblies shall comply with 820.110.
   (A)   Listing. Coaxial cables installed in buildings shall be listed.
      Exception: Coaxial cables that are installed in compliance with 820.48 shall not be required to be listed.
   (B)   Ducts Specifically Fabricated for Environmental Air. Wires and cables installed in ducts specifically fabricated for environmental air shall be installed in accordance with 300.22(B).
   (C)   Other Spaces Used For Environmental Air (Plenums). The requirements of 300.22(C) other spaces used for environmental air (plenums) shall apply.
   (D)   Risers – Cables in Vertical Runs. The following cables shall be permitted in vertical runs penetrating one or more floors and in vertical runs in a shaft:
      (1)   Types CATVP and CATVR
      (2)   Types CATVP and CATVR installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
      Informational Note: See 820.26 for firestop requirements for floor penetrations.
   (E)   Risers – Cables and Innerducts in Metal Raceways. The following cables and innerducts shall be permitted in metal raceways in a riser having firestops at each floor:
      (1)   Types CATVP, CATVR, CATV, and CATVX
      (2)   Types CATVP, CATVR, CATV, and CATVX installed in the following:
         a.   Plenum communications raceways (innerduct)
         b.   Riser communications raceways (innerduct)
         c.   General-purpose communications raceways (innerduct)
      Informational Note: See 820.26 for firestop requirements for floor penetrations.
   (F)   Risers – Cables in Fireproof Shafts. The following cables shall be permitted to be installed in fireproof riser shafts with firestops at each floor:
      (1)   Types CATVP, CATVR, CATV, and CATVX
      (2)   Types CATVP, CATVR, and CATV installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
         d.   General-purpose communications raceways
         e.   General-purpose cable routing assemblies
      Informational Note: See 820.26 for firestop requirements for floor penetrations.
   (G)   Risers – One- and Two-Family Dwellings. The following cables shall be permitted in one- and two- family dwellings:
      (1)   Types CATVP, CATVR, and CATV
      (2)   Type CATVX less than 10 mm (3/8 in.) in diameter
      (3)   Types CATVP, CATVR, and CATV installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
         d.   General-purpose communications raceways
         e.   General-purpose cable routing assemblies
      Informational Note: See 820.26 for firestop requirements for floor penetrations.
   (H)    Cable Trays. The following cables shall be permitted to be supported by cable trays:
      (1)   Types CATVP, CATVR, and CATV
      (2)   Types CATVP, CATVR, and CATV installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   General-purpose communications raceways
   (I)   Distributing Frames and Cross-Connect Arrays. The following cables shall be permitted to be installed in distributing frames and cross-connect arrays:
      (1)   Types CATVP, CATVR, and CATV
      (2)   Types CATVP, CATVR, and CATV installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
         d.   General-purpose communications raceways
         e.   General-purpose cable routing assemblies
   (J)   Other Building Locations. The following cables shall be permitted to be installed in building locations other than the locations covered in 820.113(B) through (I):
      (1)   Types CATVP, CATVR, and CATV
      (2)   A maximum of 3 m (10 ft) of exposed Type CATVX in non-concealed spaces
      (3)   Types CATVP, CATVR, and CATV installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
         d.   General-purpose communications raceways
         e.   General-purpose cable routing assemblies
      (4)   Types CATVP, CATVR, CATV, and CATVX installed in a raceway of a type recognized in Chapter 3
   (K)   One- and Two-Family and Multifamily Dwellings. The following cables shall be permitted to be installed in one- and two-family and multifamily dwellings in locations other than those locations covered in 820.113(B) through (I):
      (1)   Types CATVP, CATVR, and CATV
      (2)   Type CATVX less than 10 mm (3/8 in.) in diameter
      (3)   Types CATVP, CATVR, and CATV installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
         d.   General-purpose communications raceways
         e.   General-purpose cable routing assemblies
      (4)   Types CATVP, CATVR, CATV, and CATVX installed in a raceway of a type recognized in Chapter 3.”
6.   Revise Table 820.154(a) to read:
Applications of Listed Coaxial Cables in Buildings
Applications
Listed Coaxial Cable Type
CATVP
CATVR
CATV
CATVX
Applications
Listed Coaxial Cable Type
CATVP
CATVR
CATV
CATVX
In ducts specifically fabricated for environmental air as described in 300.22(B)
In fabricated ducts as described in 300.22(B)
N
N
N
N
In metal raceway that complies with 300.22(B)
Y*
Y*
Y*
Y*
In other spaces used for environmental air as described in 300.22(C)
In other spaces used for environmental air as described in 300.22(C)
N
N
N
N
In metal raceway that complies with 300.22(C)
Y*
Y*
Y*
Y*
In plenum communications raceways
N
N
N
N
In risers
In vertical runs
Y*
Y*
N
N
In metal raceways
Y*
Y*
Y*
Y*
In fireproof shafts
Y*
Y*
Y*
Y*
In plenum communications raceways
Y*
Y*
N
N
In riser communications raceways
Y*
Y*
N
N
In riser cable routing assemblies
Y*
Y*
N
N
In one- and two-family dwellings
Y*
Y*
Y*
Y*
Within buildings in other than air-handling spaces and risers
General
Y*
Y*
Y*
Y*
In one- and two-family dwellings
Y*
Y*
Y*
Y*
In multifamily dwellings
Y*
Y*
Y*
Y*
In non-concealed spaces
Y*
Y*
Y*
Y*
Supported by cable trays
Y*
Y*
Y*
N
In distributing frames and cross-connect arrays
Y*
Y*
Y*
N
In any raceway recognized in Chapter 3
Y*
Y*
Y*
Y*
In plenum communications raceways
Y*
Y*
Y*
N
In riser communications raceways
Y*
Y*
Y*
N
In riser cable routing assemblies
Y*
Y*
Y*
N
In general-purpose communications raceways
Y*
Y*
Y*
N
In general-purpose cable routing assemblies
Y*
Y*
Y*
N
 
Note: An “N” indicates that the cable type is not permitted to be installers in the application. A “Y*” indicates that the cable type is permitted to be installed in the application, subject to the limitations described in 820.113.
Informational Note No. 1: Part V of Article 820 covers installation methods within buildings. This table covers the applications of listed coaxial cables in buildings. The definition of Point of Entrance is in 820.2.
Informational Note No. 2: For information on the restrictions to the installation of communications cables in ducts specifically fabricated for environmental air, see 820.113(B).
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-8-830  Network-powered broadband communications systems.
   The provisions of Article 830 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise subsection 830.110(A)(2) to read:
   “Communications Raceways. Low-power network-powered broadband communication cables shall be permitted to be installed in plenum communications raceways, riser communications raceways, and general-purpose communications raceways, selected in accordance with Table 800.154(b), listed in accordance with 800.182, and installed in accordance with 800.113.”
2.   Revise subsection 830.110(C) to read:
   “Cable Routing Assemblies. Low-power network- powered broadband communications cables shall be permitted to be installed in riser cable routing assemblies, and general-purpose cable routing assemblies selected in accordance with Table 800.154(c), listed in accordance with 800.182, and installed in accordance with 800.110(C) and 800.113.”
3.   Revise subsections 830.113 (B) through (I) to read:
   “(B)   Ducts Specifically Fabricated for Environmental Air. Wires and cables installed in ducts specifically fabricated for environmental air shall be installed in accordance with.22(B).
   (C)   Other Spaces Used for Environmental Air (Plenums). Wires and cables installed in other spaces used for environmental air (plenums) shall be installed in accordance with 300.22(C).
   (D)    Risers – Cables in Vertical Runs. The following cables shall be permitted in vertical runs penetrating one or more floors and in vertical runs in a shaft:
      (1)   Types BLP, BMR, and BLR
      (2)   Types BLP and BLR installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
      Informational Note: See 830.26 for firestop requirements for floor penetrations.
   (E)   Risers – Cables and Innerducts in Metal Raceways. The following cables and innerducts shall be permitted in a metal raceway in a riser with firestops at each floor:
      (1)   Types BLP, BMR, BLR, BM, BL, and BLX
      (2)   Types BLP, BLR, and BL installed in the following:
         a.   Plenum communications raceways (innerduct)
         b.   Riser communications raceways (innerduct)
         c.   General-purpose communications raceways (innerduct)
      Informational Note: See 830.26 for firestop requirements for floor penetrations.
   (F)   Risers – Cables in Fireproof Shafts. The following cables shall be permitted to be installed in fireproof riser shafts with firestops at each floor:
      (1)   Types BLP, BMR, BLR, BM, BL, and BLX
      (2)   Types BLP, BLR, and BL installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
         d.   General-purpose communications raceways
         e.   General-purpose cable routing assemblies
      Informational Note: See 830.26 for firestop requirements for floor penetrations.
   (G)   Risers – One- and Two-Family Dwellings. The following cables shall be permitted in one- and two- family dwellings:
      (1)   Types BLP, BMR, BLR, BM, BL, and BLX less than 10 mm (3/8 in.) in diameter
      (2)   Types BLP, BLR, and BL installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
         d.   General-purpose communications raceways
         e.   General-purpose cable routing assemblies
      Informational Note: See 830.26 for firestop requirements for floor penetrations.
   (H)   Cable Trays. The following cables shall be permitted to be supported by cable trays:
      (1)   Types BLP, BMR, BLR, BM, and BL
      (2)   Types BLP, BLR, and BL installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   General-purpose communications raceways
   (I)   Other Building Locations. The following cables shall be permitted to be installed in building locations other than those covered in 830.113(B) through (H):
      (1)   Types BLP, BMR, BLR, BM, and BL
      (2)   Types BLP, BMR, BLR, BM, BL, and BLX installed in raceways recognized in Chapter 3
      (3)   Types BLP, BLR, and BL installed in the following:
         a.   Plenum communications raceways
         b.   Riser communications raceways
         c.   Riser cable routing assemblies
         d.   General-purpose communications raceways
         e.   General-purpose cable routing assemblies
      (4)   Type BLX less than 10 mm (3/8 in.) in diameter in one-and two-family dwellings
      (5)   Types BMU and BLU entering the building from outside and run in rigid metal conduit (RMC) or intermediate metal conduit (IMC) where the conduit is connected by a bonding conductor or grounding electrode conductor in accordance with 830.100(B)
         Informational Note: This provision limits the length of Type BLX cable to 15.2 m (50 ft), while 830.90(B) requires that the primary protector, or NIU with integral protection, be located as close as practicable to the point at which the cable enters the building. Therefore, in installations requiring a primary protector, or NIU with integral protection, Type BLX cable may not be permitted to extend 15.2 m (50 ft) into the building if it is practicable to place the primary protector closer than 15.2 m (50 ft) to the entrance point.
      (6)   A maximum length of 15.2 m (50 ft), within the building, of Type BLX cable entering the building from outside and terminating at an NIU or a primary protection location.”
4.   Revise Table 830.154(a) to read:
Applications of Listed Network-Powered Broadband Cables in Buildings
Applications
Listed Coaxial Cable Type
BLP
BLR
BL
BMR
BM
BLX
BMU, BLU
Applications
Listed Coaxial Cable Type
BLP
BLR
BL
BMR
BM
BLX
BMU, BLU
In ducts specifically fabricated for environmental air as described in 300.22(B)
In fabricated ducts as described in 300.22(B)
N
N
N
N
N
N
N
In metal raceway that complies with 300.22(B)
Y*
Y*
Y*
Y*
Y*
Y*
N
In other spaces used for environmental air as described in 300.22(C)
In other spaces used for environmental air as described in 300.22(C)
N
N
N
N
N
N
N
In metal raceway that complies with 300.22(C)
Y*
Y*
Y*
Y*
Y*
Y*
Y*
In risers
In vertical runs
Y*
Y*
N
Y*
N
N
N
In metal raceways
Y*
Y*
Y*
Y*
Y*
Y*
N
In fireproof shafts
Y*
Y*
Y*
Y*
Y*
Y*
N
In plenum communications raceways
Y*
Y*
N
N
N
N
N
In riser communications raceways
Y*
Y*
N
N
N
N
N
In riser cable routing assemblies
Y*
Y*
N
N
N
N
N
In one- and two-family dwellings
Y*
Y*
Y*
Y*
Y*
Y*
N
Within buildings in other than air- handling spaces and risers
General
Y*
Y*
Y*
Y*
Y*
Y*
N
In one- and two-family dwellings
Y*
Y*
Y*
Y*
Y*
Y*
N
Supported by cable trays
Y*
Y*
Y*
Y*
Y*
N
N
In rigid metal conduit (RMC) and intermediate metal conduit (IMC)
Y*
Y*
Y*
Y*
Y*
Y*
Y*
In any raceway recognized in Chapter 3
Y*
Y*
Y*
Y*
Y*
Y*
N
In plenum communications raceways
Y*
Y*
Y*
N
N
N
N
In riser communications raceways
Y*
Y*
Y*
N
N
N
N
In riser cable routing assemblies
Y*
Y*
Y*
N
N
N
N
In general-purpose communications raceways
Y*
Y*
Y*
N
N
N
N
In general-purpose cable routing assemblies
Y*
Y*
Y*
N
N
N
N
 
Note: An “N” indicates that the cable type shall not be permitted to be installed in the application. A “Y*” indicates that the cable type shall be permitted to be installed in the application subject to the limitations described in 830.113.
Informational Note No. 1: Part V of Article 830 covers installation methods within buildings. This table covers the applications of listed network-powered broadband communications cables in buildings. The definition of Point of Entrance is in 830.2.
Informational Note No. 2: For information on the restrictions to the installation of network-powered broadband communications cables in ducts specifically fabricated for environmental air, see 830.113(B).
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)
14E-8-840  Premises-powered broadband communications systems.
   The provisions of Article 840 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise 840.2 To insert the following language after the definition of “Network Terminal”:
   “Nominal Current. The designated current per conductor as specified by equipment design.
   Informational Note: One example of nominal current is 4-pair Power over Ethernet (PoE) applications based on IEEE 802.3-2015, IEEE Standard for Ethernet, that supplies current over 2 or 4 twisted pairs. The nominal current for 60-watt PoE power-sourcing equipment is 0.3 amperes per conductor, where the current in one conductor can be 0.36 amperes and another conductor can be 0.24 amperes.
2.   Revise 840.160 to read:
   “Powering Circuits. Communications cables, in addition to carrying the communications circuit, shall also be permitted to carry circuits for powering communications equipment. Installations of listed communications cables shall comply with 725.144 where listed communications cables are used in place of Class 2 and Class 3 cables.
   Exception: Compliance with 725.144 shall not be required for installations of listed 4-pair communications cables where the nominal current does not exceed 0.3 amperes in any conductor.
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1)