18-11-1107.4.1  Sheltered care facilities.
   Occupancies classified as sheltered care facilities housing more than 16 persons shall be provided with accessible features in accordance with Sections 18-11-1107.4.1.1 and 18-11-1107.4.1.2. In buildings required to have audible fire alarms, visible alarm notification appliances shall be provided in accordance with Table 1107.4.1.
Table 1107.4.1
Visible Alarms
Number of Sleeping Units
Sleeping Units with Audible Alarms
6 to 25
2
26 to 50
4
51 to 75
7
76 to 100
9
101 to 150
12
151 to 200
14
201 to 300
17
301 to 400
20
401 to 500
22
501 to 1,000
5% of total
1,001 and over
50 plus 3 for each 100 over 1,000
 
(Amend Coun. J. 7-26-06, p. 81373, § 1)