Occupancies classified as sheltered care facilities housing more than 16 persons shall be provided with accessible features in accordance with Sections 18-11-1107.4.1.1 and 18-11-1107.4.1.2. In buildings required to have audible fire alarms, visible alarm notification appliances shall be provided in accordance with Table 1107.4.1.
Number of Sleeping Units | Sleeping Units with Audible Alarms |
6 to 25 | 2 |
26 to 50 | 4 |
51 to 75 | 7 |
76 to 100 | 9 |
101 to 150 | 12 |
151 to 200 | 14 |
201 to 300 | 17 |
301 to 400 | 20 |
401 to 500 | 22 |
501 to 1,000 | 5% of total |
1,001 and over | 50 plus 3 for each 100 over 1,000 |