Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
15-26-120  Ventilation.
   Every fume or flammable compressed gas room shall have means of natural ventilation as required under Section 15-28-260 for material heating rooms. The combined area of ventilating openings with closures arranged to open automatically in case of explosion or fire shall be not less than five percent of the total wall area.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-130  Sign requirements.
   Every fume or flammable compressed gas building and every fume or flammable compressed gas room shall have the words “DANGER – POISONOUS GAS” where any fume hazard gas occurs, or the words “DANGER – FLAMMABLE GAS” where any flammable compressed gas occurs, painted in a conspicuous position on the outside of every entrance thereto; provided, however, that no such sign shall be required for any building or room in which not more than two standard cylinders of such gas are present at any time. No-smoking signs shall also be provided wherever flammable compressed gas is stored.
   Such wording shall be in plainly legible bright red letters on a white background with letters not less than six inches high and with the principal strokes thereof not less than three-fourths inch in width.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-140  Fume hazard gases – Storage and handling.
   The storage or handling of fume hazard gases shall comply with the following requirements:
   (1)   Containers having a pressure of 15 psi or less or a quantity less than 2,500 feet may be stored in suitably ventilated cabinets located outside of the main building, adequately protected from extreme heat and accumulations of snow and ice; if within a building they shall be in rooms complying with the preceding sections. No combustible material shall be allowed in such rooms or within ten feet of an outside cabinet. Quantities in excess of the above limits shall not be allowed in any building other than a fume hazard building complying with the requirements of this chapter.
   (2)   Signs having a white field with red letters four inches high and having a stroke of one-half inch shall be conspicuously posted. Such signs shall read “TOXIC GAS – HANDLE WITH CARE”.
   (3)   Defective containers which permit leakage or spillage shall be disposed of or repaired in an approved manner. No spilled materials shall be allowed to accumulate on floors or shelves.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-150  Tank storage.
   Tanks which contain more than 55 gallons of fume hazard and/or flammable compressed gases shall be located outside of any building or buried below ground level. When above ground, said tank or tanks containing liquids shall be diked. Each dike shall have a capacity of not less than one and one-half times the combined capacity of the tank or tanks it surrounds. Dike construction shall be as specified in Section 15-24-170 of this Code; provided, however, the materials of the dike walls shall be inert with respect to the materials contained within the tank or tanks.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-160  Emergency controls.
   The provisions of this section shall apply to all existing as well as newly installed tanks. All tanks, piping and fittings shall be compatible with the materials to be stored or handled. Outlets and inlets of all aboveground tanks shall have a shutoff valve as close as possible to the tank, with no branches or outlets between the tank and valve. All inlet pipes shall have an additional check valve as close as possible to the tank valve. In addition to any other valves, when the stored material is reactive with air or water there shall be a valve at each pipeline connection to any tank below the liquid level, which valve shall be effective inside the tank shell or head and can be operated manually to prevent the flow of liquid from the tank even though the pipelines are broken from the tank. All remote reach rods to valves shall be of substantial construction and shall be accessibly located and clearly marked “Emergency Shut-Off Valve”. There shall be an effective flexible connection between that tank valve and piping system or the piping shall be so arranged with swing joints to prevent stress and strain between the piping system and tank. Where the exterior piping and sides of the tank are not inert to the material being stored, the piping, piping supports and tank shall be made inert by coating or some other means to one and one-half times the height of the dike.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-170  Tank and tank cars – Safety clearances.
   Tanks or tank cars of fume hazard and/or flammable compressed gases of any capacity shall not be located within one-eighth mile from any school, institutional unit, multiple dwelling or place of public assembly.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
15-26-180  Neutralizing agents.
   Whenever a fume hazard gas and/or flammable compressed gas can be chemically changed to a less dangerous and more stable material, a qualified chemist of the manufacturer shall state in writing the safest and quickest method of changing the total capacity of the tank or tanks in case of a rupture, spillage or other emergency. The owner and/or operator of said tank or tanks shall keep sufficient quantities of the changing agent as hereinbefore determined so as to be readily available in the event of an emergency.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
Loading...