You are viewing an archived code
(a) All enclosed service spaces located within an assembly structure, including locker rooms, storage spaces, toilet rooms and similar uses, shall have walls, ceilings and floors of construction providing fire resistance of not less than one hour.
(b) Clubhouses and enclosed assembly rooms may be located only within assembly structures of noncombustible construction and shall be separated from the structure by construction providing fire resistance of not less than two hours.
(c) Garages and parking spaces for automobiles may be located only within assembly structures of noncombustible construction and shall be separated from the structure by construction providing fire resistance of not less than three hours and with no openings through such construction.
(Prior code § 55-9.1)