A five-inch clay test tee or a four-inch ABS test tee and riser shall be installed in the sanitary sewer service connection at a point just outside the easement or roadway right-of-way line and the tee component of such riser assembly shall be encased in concrete to prevent crushing thereof. All components of the test tee riser assembly shall meet the same material specifications set forth under Section 1046.14, including jointing and pipe material. The vitrified, vinyl or ABS stopper used to seal the top of the test riser shall be compatible with the specified joint selected for use and shall effectively seal the test riser against infiltration of surface water.