§ 157.136 FIRE AND EXPLOSION HAZARD.
   (A)   The storage, utilization or manufacture of materials or products ranging from incombustible to moderate burning, as determined for liquids by a closed cup flash point of not less than 187° F., is permitted subject to compliance with all other performance standards.
   (B)   The storage, utilization or manufacture of materials or products ranging from free or active burning to intense burning, as determined for liquids by a closed cup flash point of less than 187° F. but not less than 105° F., is permitted subject to compliance with all other performance standards, and providing the following conditions are met:
      (1)   The materials or products shall be stored, utilized or produced within completely enclosed buildings or structures having exterior walls of fire-resistive construction in accordance with other ordinances in the village.
      (2)   Unless otherwise provided in this chapter, all such buildings or structures shall be set back at least 60 feet from lot lines or in lieu thereof, all such buildings or structures shall be protected throughout by an automatic sprinkler system complying with installation standards prescribed by the National Fire Protection Association, or if the materials, goods or products are liquids, the protection thereof shall be in conformity with standards prescribed by the National Fire Protection Association.
   (C)   The utilization in manufacturing processes of materials which produce flammable or explosive vapor or gases, as determined for liquids by a closed cup flash point of less than 105° F., shall be permitted provided:
      (1)   That the final manufactured product does not itself have a closed cup flash point of less than 187° F.;
      (2)   That the use and storage of such materials shall be in conformity with standards prescribed by the National Fire Protection Association and with requirements of other ordinances in the village code; and
      (3)   That the storage of said materials shall be prohibited above ground.
(Ord. 77-08, passed 6-28-77) Penalty, see § 157.999