16.05.070   Section 510.7 Interior installations.
   Section 510.7 of Chapter 5 of the California Mechanical Code is amended to read:
      Section 510.7 Interior installations. In all buildings, the ducts shall be enclosed in a continuous enclosure extending from the lowest fire-rated ceiling or floor above the hood, through any concealed spaces, to or through the roof so as to maintain the integrity of the fire separations required by the applicable building code provisions. The enclosure shall be sealed around the duct at the point of penetration of the lowest fire-rated ceiling or floor above the hood in order to maintain the fire resistance rating of the enclosure and shall be vented to the exterior of the building through weather-protected openings. [NFPA 96:7.7.1.2 - 7.7.1.4]
(Ord. 5565 § 1 (part), 2022)