16.04.400   Section 1503.2.1 Locations.
   Section 1503.2.1 of Chapter 15 of the California Building Code is amended to read:
      1503.2.1 Locations. Flashing shall be installed at wall and roof intersections, gutters, wherever there is a change in roof slope or direction, and around roof openings. Where flashing is of metal, the metal shall be corrosion resistant with a thickness of not less than 0.019 inches (0.483 mm) (e.g. no. 26 galvanized sheet) and shall be primed and painted.
(Ord. 5564 § 1 (part), 2022)