Section 6004.2.1.4 and Table 6004.2.1.4 of the California Fire Code are added to read as follows:
6004.2.1.4 Quantities. The indoor storage or use of highly toxic, toxic, and moderately toxic gases in amounts exceeding the minimum threshold quantities per control area set forth in Table 6004.2.1.4 but not exceeding maximum allowable quantity per control area set forth in Table 5003.1.1(2) shall be in accordance with Sections 5001, 5003, 6001, 6004.1, and 6004.4.
Table 6004.2.1.4
Minimum Threshold Quantities for Highly Toxic, Toxic and Moderately Toxic Gases for Indoor Storage and Use
| |
Highly Toxic | 20 cubic feet |
Toxic | 405 cubic feet |
Moderately Toxic | 405 cubic feet |
(Ord. 5563 § 1 (part), 2022)