Section 5704.2.7.5.8 of the California Fire Code is amended to read as follows:
5704.2.7.5.8 Overfill prevention. An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent overfill of all Class I, II and IIIA liquid storage tanks. Storage tanks in refineries, bulk plants or terminals regulated by Sections 5706.4 or 5706.7 shall have overfill protection in accordance with API 2350.
An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent the overfilling of Class IIIB liquid storage tanks connected to fuel-burning equipment inside buildings.
Exception: Outside aboveground tanks with a capacity of 1320 gallons (5000 L) or less shall comply with Section 5704.2.9.7.5.1 (1.1)
(Ord. 5563 § 1 (part), 2022)