15.04.580   Section 5004.2.3 Containment pallets.
   Section 5004.2.3 of the California Fire Code is amended to read as follows:
      5004.2.3 Containment pallets. Combustible containment pallets shall not be used inside buildings to comply with Section 5004.2 where the individual container capacity exceeds 55 gallons (208 L) or an aggregate capacity of multiple containers exceeds 1,000 gallons (3785 L) for liquids or where the individual container capacity exceeds 550 pounds (250 kg) or an aggregate of multiple containers exceeds 10,000 pounds (4540 kg) for solids.
      Where used as an alternative to spill control and secondary containment for outdoor storage in accordance with the exception in Section 5004.2, containment pallets shall comply with all of the following:
         1.   A liquid-tight sump accessible for visual inspection shall be provided;
         2.   The sump shall be designed to contain not less than 66 gallons (250L);
         3.   Exposed surfaces shall be compatible with material stored;
      Containment pallets shall be protected to prevent collection of rainwater within the sump of the containment pallet.
(Ord. 5563 § 1 (part), 2022)