16.14.350   Section 5.307 Cooling tower water use.
   Section 5.307 Cooling Tower Water Use is added as mandatory to read:
      5.307 COOLING TOWER WATER USE
         5.307.1. Cooling Tower Water Use in Highrise Residential or Non-Residential Buildings.  
      Cooling tower water use must meet the conditions as follows and as outlined in Palo Alto Municipal Code Section 16.08.100. Projects are required to perform a potable water analysis at the site to meet the maximum concentration of parameters noted in Table 5.307.1
   Table 5.307.1
 
Ca (as CaCO3)
600 ppm
Total alkalinity
500 ppm
SiO2
150 ppm
Cr
300 ppm
Conductivity
3300 Us/cm
 
      Calculate maximum number of cycles that can be achieved with these levels of concentration shall be included in the plumbing design plans.
(Ord. 5570 § 1 (part), 2022)
Division 5.4 - MATERIAL CONSERVATION AND RESOURCE EFFICIENCY