15.04.310   Section 903.3.1.3 and 903.3.1.3.1 NFPA 13D sprinkler systems.
   Section 903.3.1.3 of the California Fire Code is amended and 903.3.1.3.1 is added to read as follows:
      903.3.1.2 NFPA 13D sprinkler systems. Where allowed, automatic sprinkler systems installed in one- and two-family dwellings shall be installed throughout in accordance with NFPA 13D and State and local standards. Fire sprinkler protection shall be provided under rear covered patios extending over 4 ft perpendicular from the exterior of the structure.
      903.3.1.3.1 Increase in fire sprinkler design criteria. Structures determined by the fire code official to have higher firefighting hazardous condition, or located in the Wildland-Urban Interface Fire Area, shall have an increase in fire sprinkler design criteria as determined by the fire code official.
(Ord. 5563 § 1 (part), 2022)