Table 105.5.9 of the California Fire Code is amended to read as follows:
TABLE 105.5.9
PERMIT AMOUNTS FOR COMPRESSED GASES1
TYPE OF GAS | AMOUNT (cubic feet)2 |
X 0.0283 for m3 |
TYPE OF GAS | AMOUNT (cubic feet)2 |
X 0.0283 for m3 | |
Carbon dioxide used in carbon dioxide enrichment systems | 875(100 lbs) |
Flammable (except cryogenic and liquefied petroleum gases) | 200 |
Highly toxic | Any amount |
Inert and simple asphyxiant | 6,000 |
Irritant | 200 |
Moderately toxic | 20 |
Other health hazards | 650 |
Oxidizing (including oxygen) | 504 |
Pyrophoric | Any amount |
Radioactive | Any amount |
Sensitizer | 200 |
Toxic | Any Amount |
Unstable (reactive) | Any amount |
For SI: 1 cubic foot = 0.0283m3.
1 Refer to Chapters 27, 30, 32, 35, 37, 40 and 41 for additional requirements and exceptions.
2 Cubic feet measured at normal Temperature and pressure.
(Ord. 5563 §1 (part), 2022)