9-2-2: DELETIONS AND CHANGES:
The following deletions and/or changes are hereby made to the NFPA 70 National Electrical Code 2014 edition.
Section 90.4 Insert: Village of Monee as authority having jurisdiction.
Section 90.4 Insert: The Fee Schedule as set forth in the building code of the Village established in Table 1 entitled Schedule of Permit Fees shall apply to all electrical work.
Section 110.5 Delete: Where other materials are used, the size shall be changed accordingly. Insert: Conductors other than copper are not allowed. Exemption: service conductors owned by utility company.
Section 210.4 (B) Insert: All switches for fire alarms, burglar alarms, exit signs, and emergency lighting shall be equipped with mechanical lockouts to prevent an accidental turnoff of the circuits.
(Ord. 1851, 5-23-2018)
Section 210.12 Delete: That the provisions of Arc-Fault Circuit Interrupter Protection.
(Ord. 1903, 3-13-2019)
Section 220.1 Insert: Provide a diagram showing service and feeders wire sizes, type of conductors, calculated loads, the area in the square feet being supplied, and demand factors shall be submitted. Required panel schedules shall show connected loads, total connected loads per phase.
Section 300.4 Insert: Except where encased in concrete, all above ground conductors shall be installed in rigid metal conduit or Electrical metallic tubing (EMT).
Section 300.5 Add (L): All conductors underground, encased in concrete, or under buildings shall be installed in PVC conduit. PVC conduit must be listed for any applicable specific locations as required in section 352.12.
Section 406.4 (D)(2) Delete: That the provisions of 406.4 (D)(2) be deleted.
Section 408.20 Location of Switchboards and Switchgear add: Anything over 800 Amps shall have two (2) means of egress with Panic Hardware.
Section 408.20.1 For all Services 800 amps or greater, sprinklers shall not be installed in electrical rooms. Additionally for all services 800 amp or more, an Electrical Room that meets all of the following, must be provided: 1). The room is dedicated to electrical equipment only, 2). Only Dry-type electrical equipment is used, 3). Equipment is installed in a 2-hour fire-rated enclosure including protection for penetrations, 4). No combustible Storage is permitted to be stored in the room.
Section 410.10 (A) add: Wall mounted exterior Fixtures shall be caulked on the top and all sides.
Section 700.16 Insert: All emergency egress lighting, illuminated exit signs, and other emergency lighting shall be of LED type.
Section 700.21 Insert: All switches for fire alarm, burglar alarm, exit and emergency lighting circuits shall be equipped with mechanical lockouts to prevent an accidental turn off of the circuits.
(Ord. 1851, 5-23-2018; amd. Ord. 1984, 8-11-2021)