§ 21-308  LOCAL LIMITS.
   (A)    An industrial waste survey is required prior to a user discharging wastewater containing in excess of the following average discharge limits:
Discharge Limit
Measurement
Type of Discharge
Discharge Limit
Measurement
Type of Discharge
0.0003
mg/l
Mercury
0.003
mg/l
Arsenic
0.003
mg/l
Cadmium
0.005
mg/l
Selenium
0.005
mg/l
Silver
0.05
mg/l
Chromium
0.06
mg/l
Copper   
0.010
mg/l
Molybdenum
0.015
mg/l
Cyanide
0.021
mg/l
Nickel
0.049
mg/l
Lead
0.175
mg/l
Zinc
25
mg/l
Ammonia
40
mg/l
TKN
100
mg/l
Oil and grease
250
mg/l
BOD
250
mg/l
TSS
500
mg/l
COD
 
   (B)   Industrial user-specific local limits for appropriate pollutants of concern shall be included in wastewater permits, and are considered pretreatment standards.
(Ord. 33-2002, passed 10-21-2002; Ord. 29-2008, passed 10- -2008)