(a) Application. The provisions of this chapter shall control the design of barriers for all residential swimming pools, spas, and hot tubs. These design controls are intended to provide protection against potential drowning and near drowning by restricting access to swimming pools, spas, and hot tubs.
(b) Outdoor Swimming Pool. An outdoor swimming pool, including an in-ground, above-ground or on-ground pool, hot tub, or spa shall be surrounded by a barrier which shall comply with the following:
(1) The top of the barrier shall be at least 48 inches (1219 mm) above grade measured on the side of the barrier which faces away from the swimming pool. The maximum vertical clearance between finished grade and the bottom of the barrier shall be 2 inches (51 mm) measured on the side of the barrier which faces away from the swimming pool. Where the top of the pool structure is above grade, such as an above-ground pool, the barrier may be at ground level, such as the pool structure, or mounted on top of the pool structure. Where the barrier is the pool structure, the structure shall have a smooth finish to eliminate potential climbing of the structure. Where the barrier is mounted on top of the pool structure, the maximum vertical clearance between the top of the pool structure and the bottom of the barrier shall be less than 4 inches (102 mm).
(2) Openings in the barrier shall be less than 4 inches (102 mm) and shall not allow passage of a 4 inch-diameter (102 mm) sphere.
(3) Solid barriers which do not have openings, such as a masonry or stone wall, shall not contain indentations or protrusions except for normal construction tolerances and tooled masonry joints.
(4) Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is less than 45 inches (1143 mm), the horizontal members shall be located on the swimming pool side of the fence. Spacing between vertical members shall not exceed 1- 3/4 inches (44 mm) in width. Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 1-3/4 inches (44 mm) in width.
(5) Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is 45 inches (1143 mm) or more, spacing between vertical members shall be less than 4 inches (102 mm). Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 1-3/4 inches (44 mm) in width.
(6) Maximum mesh size for chain link fences shall be a 2-1/4-inch (57 mm) square unless the fence has slats fastened at the top or the bottom which reduce the openings to not more than 1-3/4 inches (44 mm).
(7) Where the barrier is composed of diagonal members, such as lattice fence, the maximum opening formed by the diagonal members shall not be more than 1-3/4 inches (44 mm).
(8) Access gates shall comply with the fence requirements of this chapter, and shall be equipped to accommodate a locking device. Pedestrian access gates shall open outward away from the pool, and shall be self-closing and shall have a self-latching device. Gates other than pedestrian access gates shall have a self-closing and self-latching device. Where the release mechanism of the self-latching device is located less than 54 inches (1372 mm) from the bottom of the gate, the release mechanism and openings shall comply with the following:
A. The release mechanism shall be located on the pool-side of the gate at least 3 inches (76 mm) below the top of the gate; and
B. The gate and barrier shall have no opening larger then 1/2 inch (13 mm) within 18 inches (457 mm) of the release mechanism.
(9) Where a wall of a dwelling serves as part of the barrier, one of the following conditions shall be met.
A. The pool shall be equipped with a powered safety cover in compliance with ASTM F 1346 shall be used and in place when the pool is not in use; or
B. Doors with direct access to the pool through that wall shall be equipped with an audible alarm which produces an audible warning when the door and its screen, if present, are opened. The alarm shall be listed in accordance with UL 20 17. The audible alarm shall activate within 7 seconds and sound continuously for a minimum of 30 seconds after the door and/or its screen, if present, are opened and be capable of being heard throughout the house during normal household activities. The alarm shall automatically reset under all conditions. The alarm system shall be equipped with a manual means, such as touch pad or switch, to temporarily deactivate the alarm for a single opening. Deactivation shall last for not more than 15 seconds. The deactivation switch(s) shall be located at least 54 inches (1372 mm) above the threshold of the door; or
C. Other means of protection, such as a lockable self-closing gate with self-latching devices, which are approved by the governing body, shall be acceptable so long as the degree of protection afforded is not less than the protection afforded by Item (9)A. or (9)B. described above.
(10) Where an above-ground pool structure is used as a barrier or where the barrier is mounted on top of the pool structure and the means of access is a ladder or steps:
A. The ladder or steps shall be capable of being secured, locked or removed when the pool is not in use to prevent access; or
B. The ladder or steps shall be surrounded by a barrier which meets the requirements of Section 1359.07. When the ladder or steps are secured, locked, or removed, any opening created shall not allow the passage of a 4-inch-diameter (102 mm) sphere.
(11) Where an above-ground pool structure or a fence is used as a barrier or where the barrier is mounted on top of the pool structure, landscaping materials such as bushes, trees, rocks, bench, ornaments or other climbable items shall be a minimum of 4 feet away from the pool structure. Barriers shall be located to prohibit permanent structures, equipment, or similar objects from being used to climb them.
(Ord. 2007-032. Passed 4-10-07.)