18-29-904.5  Location of vent terminal.
   No vent terminal from a drainage system shall be directly beneath a door, window, overhead or other ventilating intake opening of the building, nor shall any such vent terminals be within 12 feet (3.66 m) horizontally of such an opening unless it is at least 2 feet (610 mm) above the top of such opening.