18-29-606.5.6  Potable water inlet control and location.
   Potable water inlets to gravity tanks shall be controlled by a ball cock or other automatic supply valve to prevent the tank from overflowing. The inlet shall be terminated as to provide an air gap not less than 4 inches (100 mm) above the overflow.