18-29-417.2  Water supply riser.
   Every water supply riser from the shower valve to the shower head outlet, whether exposed or not, shall be attached to the structure in an approved manner.
18-29-417.3  Shower waste outlet.
   Waste outlets serving showers shall be at least 2 inches (50 mm) in diameter and, for other than waste outlets in bathtubs, shall have removable strainers not less than 3 inches (75 mm) in diameter with strainer openings not less than 1/4 inch (6 mm) in minimum dimension. Where each shower space is not provided with an individual waste outlet, the waste outlet shall be located and the floor pitched so that waste from one shower does not flow over the floor area serving another shower. Waste outlets shall be fastened to the waste pipe in an approved manner.
18-29-417.4  Shower compartments.
   Shower installation, water temperature, dimensions, materials, public or institutional showers, and wall areas shall comply with Sections 18-29-417.4.1 through 18-29-417.4.7.