Pipes passing through walls and floors made of cinder, concrete, or other corrosive material shall be protected against external corrosion by a protective sheathing or wrapping or other means that will withstand any reaction from lime and acid of concrete, cinder or other corrosive material. Sheathing or wrapping shall allow for expansion and contraction of piping to prevent any rubbing action and shall be comparable with fire stops where these are required by provisions of Titles 13 and 15 . Minimum wall thickness of material shall be 0.025 inches (0.64 mm).
Notes
Titles 13 | The hyper-linked material is not part of the Chicago Building Code infobase and therefore is not included herein. The material is included in other provisions of the Chicago Municipal Code. The complete Chicago Municipal Code is available for purchase from American Legal Publishing in both print and Folio® versions. Please click here for the appropriate American Legal order form in printable Adobe® PDF format. For additional information, you may visit American Legal's website by clicking here. |
15 | The hyper-linked material is not part of the Chicago Building Code infobase and therefore is not included herein. The material is included in other provisions of the Chicago Municipal Code. The complete Chicago Municipal Code is available for purchase from American Legal Publishing in both print and Folio® versions. Please click here for the appropriate American Legal order form in printable Adobe® PDF format. For additional information, you may visit American Legal's website by clicking here. |