18-28-602.1.1  Technology centers.
   Ceiling and floor plenums may be used for supply air in Technology Centers if they are accessible for cleaning. Such supply plenums shall be limited to one fire area not to exceed 2,500 square feet. Separations between different plenums shall be made of sheet metal and sealed tight.