18-28-506.3.3.4  Vibration isolation.
   A vibration isolation connector for connecting a duct to a fan shall consist of noncombustible packing in a metal sleeve joint of approved design or shall be a coated-fabric flexible duct connector listed and labeled for the application. Vibration isolation connectors shall be installed only at the connection of a duct to a fan inlet or outlet.
18-28-506.3.4  Grease duct supports.
   Grease duct bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of the Chicago Building Code. Bolts, screws, rivets and other mechanical fasteners shall not penetrate duct walls.
18-28-506.3.5  Air velocity.
   Grease duct systems serving a Type I hood shall be designed and installed to provide an air velocity within the duct system of not less than 1,500 feet per minute (7.6 m/s).
   Exception: The velocity limitations shall not apply within duct transitions utilized to connect ducts to differently sized or shaped openings in hoods and fans, provided that such transitions do not exceed 3 feet (914 mm) in length and are designed to prevent the trapping of grease.
18-28-506.3.6  Separation of grease duct system.
   A separate grease duct system shall be provided for each Type I hood. A separate grease duct system is not required where all of the following conditions are met:
   1.   All interconnected hoods are located within the same story.
   2.   All interconnected hoods are located within the same room or in adjoining rooms.
   3.   Interconnecting ducts do not penetrate assemblies required to be fire-resistance rated.
   4.   The grease duct system does not serve solid fuel-fired appliances.
18-28-506.3.7  Clearances.
   Grease duct systems serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm).
   Exception: Listed and labeled factory-built commercial kitchen grease ducts installed in accordance with the Chicago Fire Code.