Continuous ventilation shall be provided at a rate of not less than 1 cubic foot per minute per square foot (cfm/ft
2
) [0.00508m
3
/(s x m
2
)] of floor area of the room, unless a source capture system is provided to limit the maximum concentration of hydrogen to 1.0 percent of the total volume of the room.