18-28-502.4.2  Ventilation rate.
   Continuous ventilation shall be provided at a rate of not less than 1 cubic foot per minute per square foot (cfm/ft 2 ) [0.00508m 3 /(s x m 2 )] of floor area of the room, unless a source capture system is provided to limit the maximum concentration of hydrogen to 1.0 percent of the total volume of the room.