Skip to code content (skip section selection)
Compare to:

You are viewing an archived code

18-28-401.5.1.5  Relief openings.
   Relief openings (RO) as used in Table 18-28-403.3 as set out in Section 18-28-403.3, shall be considered to be any duct that connects a room to the outside. Relief openings for ductwork shall be of sufficient cross sectional area so that maximum velocity shall not exceed 800 feet per minute. Relief openings in ducts for exhaust may extend in a horizontal direction for a distance not to exceed 5 feet.