14E-3-336  Power and control tray cable: Type TC.
   The provisions of Article 336 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise subsection 336.10, item (1) to read:
   “For control and signal circuits.”
2.   Delete subsections 336.10, items (6) through (10).
3.   Revise section 336.12 to read:
   “Uses Not Permitted. Type TC tray cable shall not be installed or used as follows:
   (1)   Installed where it will be exposed to physical damage
   (2)   Installed outside a raceway or cable tray system
   (3)   Used where exposed to direct rays of the sun, unless identified as sunlight resistant
   (4)   Direct buried
   (5)   Required fire alarm systems
   (6)   In health care facilities, any patient communication or monitoring system”
(Added Coun. J. 9-6-17, p. 55278, Art. I, § 1; Amend Coun. J. 11-8-17, p. 59720, § 15)