The strength of engineered brick and concrete masonry fm shall be verified by field tests made in accordance with Section 4.2 of SCPI 1969 for engineered brick masonry and Section 3.2 of NCMA 1970 for engineered concrete masonry. A minimum of one field test specimen shall be made during construction for each 2,000 square feet of wall. A minimum of two tests shall be made for each building, one at the start of construction and one when at least 50 percent of the masonry has been completed.
(Prior code § 71-6)