15-16-1380  Zoned systems.
   A zoned-type fire alarm system, with zones not exceeding 20,000 square feet or serving more than one floor, shall be required under any one of the following conditions:
   (a)   When the building exceeds four stories in height;
   (b)   When any side of the building is 200 feet or more in length;
   (c)   When the system has more than eight manual alarm-sending stations;
   (d)   When more than ten automatic detectors are connected to the standard fire alarm system, unless the alarm system serves only a Type III school occupying only the first floor of a building;
   (e)   When the ground floor area of the building exceeds 20,000 square feet.
(Prior code §  91-116; Amend Coun. J. 3-15-91, p. 31145)