15-8-210  Two-hour protection required.
   Rooms containing heating plants or steam boilers shall be enclosed with walls, partitions, floors and ceilings of noncombustible construction providing fire resistance of not less than two hours under the following conditions:
   (a)   Rooms containing steam boilers carrying a pressure of more than 15 pounds per square inch and having a rating in excess of ten boiler horsepower;
   (b)   Rooms containing heating plants or steam boilers in buildings having a capacity exceeding 200 persons;
   (c)   Rooms containing heating plants or steam boilers in institutional units.
(Prior code §  62-4.2)