Installation of bulk oxygen systems shall be supervised by personnel familiar with proper operating practices. All installations shall be field tested and proved gastight at maximum operating pressure.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)
The bulk oxygen storage location shall be permanently placarded to read:
Oxygen
No Smoking
No Open Flames
Lettering shall be in accordance with Section 15-26-130 of this Code.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)