13-68-020  Ventilation of intermediate offices.
   (a)   Definition. An intermediate office is a room or space used for business purposes enclosed by partitions and having no direct openings to the outside air for natural ventilation.
   (b)   Natural Ventilation. Except when mechanical ventilation is provided, intermediate offices shall be provided with natural ventilation as herein required.
      (1)   An intermediate office shall have doors or other openings of not less than 15 percent of the floor area of the intermediate office opening into a room or space having a direct source of natural ventilation. The area of such direct source of natural ventilation shall comply with the requirements of Chapter 13-172 applied to the combined floor areas.
(Prior code § 56-2)