a. The minimum number of fire hydrants needed to deliver the required fire flow for the protection of buildings, or portions of buildings, hereafter constructed shall be in accordance with National Fire Protection Association (NFPA) 1, Fire Code, 2012 Edition, Annex E, Fire Hydrant Locations and Distribution, which is hereby adopted and incorporated, except as specifically amended, modified, or deleted in this Chapter.
b. The aggregate fire flow capacity of all fire hydrants within one thousand (1,000) feet of the building, as measured along fire department access roads, shall be not less than the required fire flow determined in accordance with Section 12-4.02.
(Ord. BG2021-15, 5/4/2021)